Side Pipe Routing
The direction (in step 2) in which the main
pipes are tightened by using hold hoops is for
reference only. The onsite situation prevails.
1. Remove the pipe clamp securing the
vertical pipe using a Phillips screwdriver.
(Install the removed pipe clamp to the
cabinet side door in step 7.)
2. Remove the elbow hoops securing the
horizontal pipe using a 15# socket wrench,
and then take out the bend.
3. Remove the hold hoop securing the bend
using a 15# socket wrench. To avoid
deforming the pipe, use a 75# open-end
wrench to fix the pipe nut, use a 36# open-
end wrench to fix the plug, and then
remove the plug.
4. Connect the threaded connecting ends
removed from the straight pipe to the
external pipe (apply thread sealant on the
joints of external screw threads), and
secure them using a 75# open-end wrench
and an 18# pipe wrench.
5. Route the other end of the straight pipe
through the side door to the pipe of the
smart cooling product using a black
sealing ring (seal the pipe connection point
using a black sealing ring).
6. Secure the pipe using hold hoops.
7. Attach thermal insulation foam to the pipe,
and then install the pipe clamp on the side
panel of the NetCol8000-C using a Phillips
screwdriver to secure the pipe. Wrap the
pipes with thermal insulation foam after
installing the pipes.