3.2
Removing the Pallet
1. For a single-door and double-dour cabinet, remove the four screws from both sides.
2. For downflow units, remove the fan maintenance baffle plate at the front door before removing
the bolts.
Open the front
door and remove
the rear door.
Remove the bolts
that secure the
cabinet and the
pallet using a 19#
socket wrench.
(Optional) Cabinet Assembly (Applicable only to Downflow
3.3
Units with Four Doors)
1. Operations should be conducted in a spacious and safe environment.
2. After the cables are connected, mark the terminals and bind them along the cabinet beam using
cable ties.
3. Ensure that nitrogen is completely exhausted from the exhaust valves of all modules.
1. Remove the side protection cardboards and rear door panels of
module 2 and module 3. Open the front doors of module 2 and
module 3, and remove the fan protective cover.
2. Use quick release screws to secure the front and rear columns
of the module 2 and module 3 to assemble the unit.
3. Use a 15# socket wrench to remove
the hold hoop that secures the main
pipe, remove the black sealing ring,
and remove the pipe plug.