In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:

Advertisement

4.10
(Optional) Teamwork Settings
The default networking mode is CAN network.
If the CAN teamwork function needs to be enabled onsite, set Teamwork CAN resistor enable
for the first and last smart cooling products to Yes over the LCD.
Smart cooling products in a teamwork group must be of the same model.
The following figures show how to make the teamwork and monitoring network cables.
If the two-wire system is adopted for northbound RS485 monitoring onsite, only RS485 T+(D+) and
RS485 T-(D-) pins need to be crimped.
Main Control Module
(1) FE_1 (reserved)
(2) CAN_IN (input port of the teamwork CAN and northbound RS485 ports)
(3) RS485/12 V (T/H module port)
(4) Main control module handle
(5) SW (reserved)
(6) DIP switch
(7) COM (northbound RS485 port)
(8) CAN_OUT (output port of the teamwork CAN and northbound RS485 ports)
(9) FE_2 (for FE teamwork)
(10) Alarm indicator
(11) Run indicator
(12) Power indicator
21