24 Electrical installation

Installing power and ground cables

NOTICE
Waste inside the cabinet can cause damage or malfunction.
High voltages will be present in the terminal compartment. High voltages can
cause flashover between the electric potential of different conductors, and the
electric potential of a conductor and earth.
Therefore, do not cut cables inside the terminal compartment. Retrieve any waste
dropped into the cabinent.
Prepare the cable termination as illustrated in the figure below. The conductor screen must
be connected to the PE ground busbar. It is prohibited to cut off.
1
2
3
4
5
Outer cable sheath
Entry plate
Conductor screen extension to be
connected to PE ground busbar
Heat-shrinkable termination
Sealing compound
1
2
5
3
4