Fujitsu ETERNUS AF Series Configuration Manual page 39

All-flash arrays, hybrid storage systems, disk storage systems, power synchronized unit
Hide thumbs Also See for ETERNUS AF Series:
Table of Contents

Advertisement

2.
Installation
Installing in a Rack
■ Procedure for installing an AC sensor unit
Procedure
1
Open the front and rear doors of the rack.
2
Attach the M6 cage nuts to the rear rack pillar.
Attachment positions
Insert four M6 cage nuts in the 1st and 3rd holes above the AC sensor unit base line.
Attachment procedure
Clip the M6 cage nut tabs into the desired hole from the inside.
Top view
3
Attach the L-shaped brackets to the AC sensor unit.
Use four M3 cross recessed head screws with captive washer to attach the L-shaped brackets to the AC sen-
sor unit on both sides.
M3 cross recessed head
screws with captive washer
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
(Rear rack pillars)
3rd position
1st position
Base line of AC sensor unit
M6 cage nut
Rack pillar (square)
L-shaped bracket
L-shaped bracket
Copyright 2019 FUJITSU LIMITED
1U (AC sensor unit size)
M3 cross recessed head screws
with captive washer
39
P3AM-8012-14ENZ0