4.1.3

Status and error display of SINAMICS Integrated

RDY LED states
Table 4- 2
LED flashes green
LED flashes yellow
LED flashes yellow
LED flashes red
LED flashes green-
LED flashes red-
SIMATIC Drive Controller
Equipment Manual, 11/2019, A5E46600370-AA
Interrupts, diagnostics alarms, error messages and system alarms
SINAMICS Integrated RDY LED
RDY LED
Meaning
Electronics power supply is missing or is outside the permissible tolerance
range
LED off
The component is ready for operation.
LED lit green
Cyclic DRIVE-CLiQ communication is active or SINAMICS Integrated is wait-
ing for first commissioning.
Commissioning/reset
(0.5 Hz)
System is booting and DRIVE-CLiQ communication is being established.
LED lit yellow
Firmware update of components is complete, waiting for POWER ON of the
component.
Remedy: Perform POWER ON of the respective component
(2 Hz)
Firmware update of the connected DRIVE-CLiQ components in progress.
(0.5 Hz)
Component has at least one fault.
LED lit red
General errors
Remedy: Check parameter assignment/configuration
(2 Hz)
Firmware could not be started. (for example, update error, drive firmware not
compatible with CPU or missing, CRC check failed)
Component detection via LED is activated (p0124[0]).
Note
The two possibilities depend on the status of the LED at time of activation via
yellow
p0124[0] = 1.
(2 Hz)
yellow
(2 Hz)
4.1 Status and error displays
65