Mitsubishi Electric MELSEC iQ-R Series User Manual page 28

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

RAS
RAS stands for Reliability, Availability, and Serviceability. This function improves overall usability of automated equipment.
Function
Device station disconnection
Automatic return
Loopback function
Master station duplication
detection
IP address duplication detection
Time synchronization
Synchronous communications
This function adjusts the timing with the timing of different device stations connected on the same network.
Function
CC-Link IE TSN network
synchronous communication
function
Safety communications
This function allows safety data to be exchanged between safety stations on the same network.
Function
Safety communications
Troubleshooting
This function checks the status of modules and networks by executing diagnostics and operation tests using the engineering
tool.
Function
Module communication test
CC-Link IE TSN/CC-Link IE Field
diagnostics
Communication test
3 FUNCTION LIST
26
Description
Stops data link of the station where an error occurred, and
continues data link only for stations that are operating
normally.
Restarts the data link automatically when the device station
that was disconnected due to an error becomes normal
again.
Continues data link with normally operating stations even if
a cable disconnection or faulty station occurs in a ring
topology network configuration.
If one network has multiple master stations, duplication is
detected.
If one network has stations with the same IP address,
duplication is detected.
This function synchronizes the time of device stations with
the time synchronization source (CPU module of the
master station).
Description
Synchronizes control cycles between device stations over
CC-Link IE TSN according to the inter-module
synchronization cycle specified in the master station. This
allows different device stations on the same network to
operate with the same timing.
Description
Establishes a safety connection and enables one-on-one
safety communications periodically between safety
stations in the same network.
Description
Checks the module hardware when communication using
the RJ71GN11 is unstable.
Monitors the status of CC-Link IE TSN. The network maps,
stations where data link is not operating, selected station
communications status monitor and so on are displayed on
the engineering tool.
Checks if transient transmission data can be properly
routed from the own station to the communication target.
RJ71GN11-T2
RJ71GN11-SX
Master
Local
Master
station
station
station
RJ71GN11-T2
RJ71GN11-SX
Master
Local
Master
station
station
station
RJ71GN11-T2
RJ71GN11-SX
Master
Local
Master
station
station
station
RJ71GN11-T2
RJ71GN11-SX
Master
Local
Master
station
station
station
Local
station
Local
station
Local
station
Local
station

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rj71gn11-t2Rj71gn11-sx

Table of Contents