Setting in the master station

Connect the engineering tool to the CPU module on the master station and set the parameters.
1.
Set the CPU module as follows.
[Project]  [New]
2.
Click the [Setting Change] button and set the item that is to use module labels.
3.
Set "Link Direct Device Setting" in "CPU Parameter" to "Extended Mode (iQ-R Series Mode)".
[CPU Parameter]  [Memory/Device Setting]  [Link Direct Device Setting]  [Link Direct Device Setting]
To write module parameters of the RJ71GN11-T2 on a CPU module using an engineering tool, set "Link Direct
Device Setting" to "Extended Mode (iQ-R Series Mode)".
If "Link Direct Device Setting" is "Q Series Compatible Mode", "Write to PLC" cannot be executed.
8 COMMUNICATION EXAMPLES
74
8.1 RJ71GN11-T2 Communication Example