• Connect the master station and local station at the same communication speed.
No.0
Class B (100Mbps)
No.1
Class B (100Mbps)
No.0: Master station
No.1, No.2: Local station
No.3: Remote station
Class B: CC-Link IE TSN Class B device
• When "Communication Mode" is set to "Multicast" and the communication speed of the master station is 1Gbps,
communication may not be possible depending on the type of the device if device stations with 1Gbps and 100Mbps
coexist on the end side via the switching hub. The communication will be enabled by configuring settings with the switching
hub so that the multicast frame (with multicast MAC address 09:00:70:00:10:02 and 09:00:70:00:10:05) will not be
transferred to the port of the device station with 100Mbps.
No.0
Class B (1Gbps)
No.1
Class A (100Mbps)
No.0: Master station
No.1, No.2: Remote station
No.3: Local station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
5 SYSTEM CONFIGURATION (RJ71GN11-T2)
56
5.2 Structure with CC-Link IE TSN Class B/A Devices
No.2
Class B (100Mbps)
No.3
Class A (100Mbps)
No.2
Class A (100Mbps)
No.3
Class B (1Gbps)
No.0
Class B (1Gbps)
No.1
Class B (100Mbps)
No.2
Class B (100Mbps)
No.3
Class A (100Mbps)