The IEC 61850 standard describes in part 7–2 the ACSI in a media and protocol independent form.
Part 8–1 specifies the mapping of this ACSI to the existing MMS.
The communication section describes how information is routed between the IEDs and contains the
following parts:
Subnetworks
IEDs connected to different subnetworks
Access points per IED to subnetworks
Address
IP address of LAN network (is exceptionally part of the address elements)
Link to GoCB message in transmission direction (extended during signal engineering and
routing)
Subnetwork
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IEC06000101 V1 EN-US
Figure 3:
Additional information about the server is part of the IED.
3.3

The IED section

The IED section describes the complete IED as it is needed for IEC 61850 communication and signal
engineering. The data type template part of an IED may be seen as part of the IED, even when
separated in its own section. The IED's ICD files include the description of the logical nodes, their
data type templates and the used or supported services. The structure of the IED section follows the
definitions made in the IEC 61850 standard.
Two basic IED types are used in system configuration.
Station level IEDs
are located on the station level and are identified as client IEDs when they read or write
information from or to the bay IEDs. This functionality is represented by logical nodes of group
"Information (I)". These are the logical nodes (LN) = ITCI, IHMI and ITMI. Client IEDs are the
Switchgear control unit SAM600-IO
Communication protocol manual
IED
(client)
- Access Point (AP)
- Address
- GSE; GoCBs
Communication
AP
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
IEC 61850–6: Communication network
The LPHD.PhyHealth reflects the physical health of the IED. The status is set to
Alarm when there is an internal failure in the IED or Warning if any active
communication link fails.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IED
(client)
- Access Point (AP)
- Address
- GSE; GoCBs
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
Substation Configuration description Language (SCL)
AP
Communication
IED
(server)
en06000101.vsd
Section 3
SEMOD129775-4 v9
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sam600-io

Table of Contents