Table 14. Environmental and safety standards (continued)
Operating temperature
Storage temperature
Transit temperature
Relative humidity
Operating altitude
Transit altitude
Audible noise
Table 15. Battery
Rack / Tower configuration
Type
Monitoring
Battery port
EBM battery cable length
Table 16. Communication options
Communication bay
Compatible connectivity cards UPS Network Management Card
Communication ports
Relay output contacts
Remote On/Off
Remote Power Off
48
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: Thermal protection switches load to Bypass in case of overheating.
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 45 dBA at 1 meter typical
Internal batteries
5000/6000VA: 180Vdc
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float
service life at 25°C (77°F).
Lifetime is reduced above 30°C.
Advanced monitoring for earlier failure detection and warning
External three-pole SBS75G Black connector on UPS for connecting to EBM
40cm (15.7in)
(1) available independent communication bay for connectivity cards
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
(4) relay outputs (normally open or normally closed)
2 pins jumper (normally open)
3 pins jumper (normally open or normally closed)
EBMs
5594-6BX: 180Vdc