Creating Disturbance Recordings; Monitoring Disturbance Recorder Data - Hitachi 650 Series Operation Manual

Hide thumbs Also See for 650 Series:
Table of Contents

Advertisement

Section 7
Operating procedures
7.1.3.1

Creating disturbance recordings

Normally disturbance recordings are triggered by the IED applications but the recording can also be
triggered manually.
1.
Select Main menu /Disturbance records .
2.
Select Manual Trig with
3.
Press
GUID-D18A9DC0-4392-4BAF-86D0-C43F2714B428 V1 EN-US
Figure 36:
The disturbance recorder is now triggered.
7.1.3.2

Monitoring disturbance recorder data

Read individual disturbance recordings from the IED with the PCM600 software to monitor
disturbance recorder data.
1.
Select Main menu /Disturbance records .
All disturbance records are listed.
2.
Scroll the view with
54
Set the DRPRDRE Operation to On via LHMI or PCM600 and at least one channel has to
be connected. To make the setting, select Main menu /Settings /IED Settings and then
Monitoring /Disturbance report /DisturbanceReport /DRPRDRE:1 .
or
to execute manual triggering.
Manual triggering
or
.
© 2017 - 2023 Hitachi Energy. All rights reserved
.
IEC13000261-1-en.vsd
1MRK500128-UEN Rev. H
GUID-B0CE46C1-1219-4BA2-9627-E53FC0413409 v5
GUID-CBA8221F-A0F8-4043-98D7-577830F29F7F v6
650 series
Operation manual

Advertisement

Table of Contents
loading

Table of Contents