Section 7
Operating procedures
1.
Press
All the items that can be cleared are shown.
GUID-0CFAED62-312B-449F-BB58-D49496EA1CC8 V2 EN-US
Figure 41:
The content of the Clear menu depends on the configuration configured with PCM600.
2.
Select the item to be cleared with
3.
Press
4.
To clear other items, repeat the steps.
7.4

Changing the IED functionality

7.4.1

Defining the setting group

7.4.1.1

Activating a setting group

IED settings are planned in advance for different operation conditions by calculating setting values to
different setting groups. The active setting group can be changed manually from the menu or by the
PCM600 tool.
1.
Select Main menu /Settings /Active setting group /SETGRPS:1 and press
58
to activate the Clear view.
Clear view
, select OK to confirm the selection or Cancel to cancel the selection.
Do not switch off the auxiliary power supply to the IED before changes, for example,
setting parameter or local/remote control state changes are saved.
Do not switch off the auxiliary power supply to the IED before changes. For example,
when setting parameter changes are saved.
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC13000236-1-en.vsd
or
.
1MRK500128-UEN Rev. H
GUID-A9853F1B-78ED-4AEF-AAE2-C27FF3DAE408 v3
AMU0600439 v8
.
650 series
Operation manual