1MRK500128-UEN Rev. H
Table 15:
Headline
Incorrect setting of SyncLostMode
Sampled value substituted
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag
or parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM rate (2M) is not supported
LDCM version is not accepted
SFP unplugged from the slot
SFP replaced with other type
Table continues on next page
650 series
Operation manual
Hint menu
© 2017 - 2023 Hitachi Energy. All rights reserved
Explanation
There are two explanations possible:
SyncLostMode is set to Block, no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless
a UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Energy _MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Energy _MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Energy _MU0101>
The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid
reference channel.
At least one of the access points configured for GOOSE
is disabled. The port can be disabled either through
changing the access point operation to off or by
unchecking the GOOSE protocol from the access point
in the Ethernet configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT,
AP_1, AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
LDCM in <slot number> is running the factory image
instead of the application image. The factory image is
older than the required FW version and does not contain
the latest updates and fixes.
Reboot the IED. If the problem persists, update the
LDCM firmware or replace the board.
The <firmware version> does not support 2M mode. Set
the LDCM to 64k bit mode.
<device name> firmware version <version string> is not
accepted. The minimum accepted version is <version
string>.
Update the LDCM firmware or replace the board.
SFP has been unplugged from the slot.
Check the connection.
Corresponding hardware(s) is set to fail.
Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Restart IED and consider reconfigure of HW modules in
LHMI path: \Main menu\Configuration\Reconfigure
HW modules to get the updated hardware list.