6.8
Installing a Genset Control Signal Cable
For a generator set (genset) that starts when the dry contact is open, connect the signal
cable to ports NC and COM. For a genset that starts when the dry contact is closed, connect
the signal cable to ports NO and COM.
In the genset + mains scenario, the ATS must support the mains detection function. Connect
the mains detection cable of the ATS to the dry contact port DIN1.
Genset-Only Scenario
Genset + Mains Scenario
Genset
Genset
ATS
21