Huawei iSitePower-M Quick Manual page 4

Hide thumbs Also See for iSitePower-M:
Table of Contents

Advertisement

1.2
Recommended battery configuration
Maximum capacity: In a single-node system, a maximum of six battery modules can be
connected. In a parallel system, a maximum of three power modules can be connected. Each
power module can connect to a maximum of three battery modules.
In a parallel system, three routes of single-phase output can be combined but they cannot
be used as three-phase output.
In a parallel system, the number of battery modules on the master and slave products must
be the same.
In a parallel system, if the number of battery modules on the master and slave products are
different (not recommended), the products with larger capacity may fail to fully discharge in
heavy load scenarios.
In a system with one power module and one battery module, when the ESS supplies power
independently, the load power cannot exceed 2.5 kW. If the load power exceeds 2.5 kW, the
ESS shuts down for 10 seconds and then restarts, which repeats for three times. The ESS runs
with a power limit of 2.8 kW for 1 hour and then stops working.
Scenario
Single-node system
Single-node system
(capacity expansion
scenario)
Parallel system
Overview
Number of Power
Modules
1
2
3
Number of Battery
Modules
1
2
3
4
5
6
2
4
6
3
6
9
3
Maximum Output
Power
2.5 kW
5 kW
5 kW
5 kW
5 kW
5 kW
5 kW
9 kW
9 kW
7.5 kW
13.5 kW
13.5 kW
Power
5 kWh
10 kWh
15 kWh
20 kWh
25 kWh
30 kWh
10 kWh
20 kWh
30 kWh
15 kWh
30 kWh
45 kWh