MULTI V Water IV
5. Field Wiring
Example Connection of Communication Cable
 Single Outside Unit - 3Ø, 380-415V / 380V
Outside
Power supply
(3Ø 4wires)
(Main Switch)
Indoor
Power supply
(1Ø 2wires)
L
N
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
WARNING
Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
Install the main switch that can interrupt all the power sources in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on
and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU.B SODU.A
The GND terminal at the main PCB is a '-' terminal for day contact,
it is not the point to make ground connection.
Heat Pump
[Outside Unit]
R S T N
Switch
Fuse
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
IDU.B
IDU.A
CEN.B
3
4
3
4
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
(Installer option)
(Installer option)
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
CEN.A
DRY1
DRY2
GND
12V
3
4
Outside Units
Voltage range(V)
Frequency
Outside
Indoor
60Hz
380V
220V
50Hz
380~415V 220~240V
Master
Outdoor Unit
19