Heat pump 380-415v + 380v r410a(50hz/60hz)

Advertisement

MULTI V Water IV
6. Installation
6.1 The location of the Anchor bolts
62
WARNING
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
Have installation work in order to protect against a strong wind and earthquake. Any installation
deficiency may cause unit to fall down, resulting in a personal injury.
Especially take care for support strength of the floor surface, water drain processing (processing of
water flown out from the outside unit during operation) and paths of the pipe and wiring when making a
base support.
6.2 Refrigerant piping Installation
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Step 1) Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the outside unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
Heat Pump
755
632
632
62
Copper
tube
90°
The location of
anchor bolt
Slanted Uneven Rough
Installation of Outside Units
9

Advertisement

loading

This manual is also suitable for:

Multi v water iv0cvt0-01n