8. Refrigerant Piping System
Pipes between outside units are 2 m(6.6 ft) or longer
If the distance between the outside units becomes more than 2 m (6.6 ft), apply Oil Traps between the gas pipes
If the outside unit is located lower than the main pipe, apply Oil Trap
Heat Pump
2 m(6.6 ft) or less
Oil Trap
2 m(6. 6 f t ) or l e ss
2 m(6.6 ft) or longer
Oil Trap
0.2 m(0.66 ft) or more
2 m(6.6 ft) or longer
Oil Trap
2 m(6.6 ft) or l e ss
2 m(6.6 ft) or longer
Installation of Outside Units
29