Download Print this page

LG 0CVW0-01O Manual page 376

Heat pump 380-415v + 380v r410a(50hz/60hz)

Advertisement

MULTI V Water IV
9. Electrical Wiring
9. Electrical Wiring
9.1 Areas of Caution
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
WARNING
Be sure to have authorized Electrical engineers do electric work using special circuits in accordance with
regulations and this installation manual. If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.
2. Install the outside unit transmission line away from the power source wiring so that it may not affected by electric
noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outside unit.
CAUTION
Be sure to correct the outside unit to earth. Do not connect earth line to any gas pipe, water pipe,
lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of indoor and outside units, because the box is sometimes
removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will be
burnt out.
6. Use 2-core shield cable for transmission line.(
systems are wired with the same multiplecore cable, the resultant poor transmission and receiving will cause
erroneous operations. (
7. Only the transmission line specified should be connected to the terminal block for outside unit transmission.
Outside Unit
2-core shield cable
Heat Pump
mark in the figure below) If transmission lines of different
mark in the figure below)
Indoor
Indoor
Unit
Unit
Remote
Remote
control
control
Indoor
Indoor
Unit
Unit
Remote
Remote
control
control
Installation of Outside Units
Outside Unit
Indoor
Unit
Outside Unit
Indoor
Unit
Multi-core cable
Indoor
Unit
Remote
Remote
control
control
Indoor
Unit
Remote
Remote
control
control
37

Advertisement

loading

This manual is also suitable for:

Multi v water iv0cvt0-01n