6.3

Terminal function selection

6.3.1 Changing control logic switching
 : Sink/source switching selection
• Function
Control input/output terminal sink logic (minus common)/source logic (plus common) is switched.
■ Parameter settings
Title
 Sink/source switching
* 1: Depends upon the setup menu settings.
Sink/source settings are basically selected on the setup menu. (See 3.1.)
After selecting them on the setup menu, the parameters are used for switching sink/source. However,
disconnect the control circuit terminals of the inverter. Otherwise, the equipment may malfunction.
After setting  switching, the check alarms (  ,  ) are displayed, reset panel, external
signal, or power.
See pages B-9 and B-10 regarding sink/source logic connections.
6.3.2
Keeping an input terminal function always active (ON)
 : Always-active function selection 1
 : Always-active function selection 2
• Function
This parameter specifies an input terminal function that is always to be kept active (ON).
Parameter setting
Title
Always-active function selection 1


Always-active function selection 2
Function
0: Sink
100: Source
1-99, 101-255: invalid
Function
0-123 (See 11.6.)
0-123 (See 11.6.)
F-7
Adjustment range
Adjustment range
Default setting
0 (No function)
E6581595
Standard
defaults
*1
6
6 (Standby)