Spring Terminal Blocks
1. Power terminal block
Max. cable length: 10 m
(35 ft)
Cable type: 4~10mm² (10~12
AWG)
DC 600V insulated
Pinning
Phoenix contact
PCB terminal block SPT
5/3-H-7,5-ZB
P/N: 1719202
2. Communication terminal block
Max. cable length: 10 m
(35 ft)
Cable type: 0.2~1.5mm²
(18~22AWG)
Pinning
Phoenix contact
PCB terminal block SPT
2,5/6-H-5,0
P/N: 1991011
terminal cable).
NOTE
the battery and/or inverter.
4. Section E: Battery power port
a) Connect the ground wire to
Terminal 2.
b) Connect the negative line of the
power cable to Terminal 3.
c) Connect the positive line of the
power cable to Terminal 1.
Blocks when choosing the battery
power cable and cable sheath for
peeling.
( + )
GND
( - )
ENABLE 12V
ENABLE GND
RS485 A+
RS485 B-
CAN Hi
CAN Lo
4 Commissioning
4.1 LED Indicators
The LED indicators on the front of the battery pack show its operational state as follows:
LED 1
LED 2
LED 3
(Power)
(Charge)
(Discharge)
-
-
-
-
-
-
-
-
-
-
(Every 10 s)
-
-
-
-
-
(Quickly)
-
There are four LED indicators on the front of the battery packs to show its operating status.
1. Power On(Init) : Initialization for operating the battery
2. Ready : Battery is ready for operating normally.
3. Charge : Battery pack is charging.
4. Discharge :Battery pack is discharging.
5. Fault : Battery pack is warning state. Fault1 is blinking. Fault 2 is continuous. See
Section 5 Troubleshooting guide for detail condition.
6. Power saving : Battery stay in minimum self consumption power mode.
7. FW update : Battery is in update sequence. See the detail LED indication about
Updating, Update complete, Update failed.
4.2 Powering On the Battery Pack
Power on the battery through the following steps:
1. Open the front cover.
2. Ensure the circuit breaker switch is in the OFF position.
3. Turn on the circuit breaker.
4. Seconds after the circuit breaker switch is ON, four (4) LED indicators will light
up.
5.
successfully initialized. The LED power indicator on the front should be green.
6. Close the front cover.
7. Turn on the inverter.
CAUTION
Electronics or your distributor.
1.
2. Open the front cover.
3.
position.
4. Make sure that every LED indicator on the battery pack is OFF. (After 10
5. Close the front cover.
LED 4
Status
(Fault)
Power on (lnit)
-
Ready
-
Charge
-
Discharge
Fault 1
Normal
Fault 2
-
Power-saving
-
-
Updating
FW Update
Update
-
Complete
Update Failed