1MRK500127-UUS Rev. M
Table 12:
Function
Authority status
ATHSTAT
Authority check
ATHCHCK
Authority management
AUTHMAN
For more information on Authority management AUTHMAN, Authority status ATHSTAT, and Authority
check ATHCHCK functions, see Chapter Basic IED functions in technical manual.
At delivery, the IED has a default user defined with full access rights. PCM600 uses this default user to
access the IED. This user is automatically removed in IED when users are defined via the IED Users tool
in PCM600.
Default User ID: Administrator
Password: Administrator
See the Cyber security guideline for information on cyber security.
4.3

Communication

The IED supports the following communication protocols: IEC 61850-8-1, IEC/UCA 61850-9-2LE , SPA,
IEC 60870-5-103, LON, DNP3, C37.118 and IEEE1344.
All operational information and controls are available through these protocols. However, some
communication functionality, for example, horizontal communication between the IEDs, is only enabled
by the IEC 61850-8-1 communication protocol (GOOSE) and as Network Variables on LON.
670 series
Operation manual
After three consecutive failed login attempts the user will be locked out for ten minutes before
a new attempt to login can be performed. This time is settable 10 minutes to 60 minutes.
The PCM600 caches the login credentials after successful login for 15 minutes. During that
time no more login will be necessary.
Authority-related IED functions
Description
This function is an indication function block for user logon activity.
User denied attempt to log-on and user successful logon are reported.
To safeguard the interests of our customers, both the IED and the tools that are accessing the
IED are protected, by means of authorization handling. The authorization handling of the IED
and the PCM600 is implemented at both access points to the IED:
local, through the local HMI
remote, through the communication ports
The IED users can be created, deleted and edited only in the CAM server.
This function enables/disables the maintenance menu. It also controls the maintenance menu
log on time out.
For user management, see Cyber security deployment guideline.
Only characters A - Z, a - z and 0 - 9 shall be used in user names. User names are not case
sensitive. For passwords see the section Password policies.
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 4
Overview
GUID-75BBAD63-2CA0-4169-97C8-2EC31C945FF4 v1
GUID-12C44065-8E0C-4456-9C6E-0BD2D58C215B v11