How To Set Frequency And Voltage And Current Gain Factors - Hitachi Relion 670 Series Operation Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 8
REX060 injection unit LHMI
Column
Column
Row
Row
1
1
2
2
3
3
4
4
5
5
IEC10000334 V2 EN-US
Figure 62:
Column 1 (status column) symbols
Table 16:
Status symbol
IEC10000329 V1 EN-US
IEC10000330 V1 EN-US
IEC10000332 V1 EN-US
Backlight is on for 30 seconds after pressing any button. Backlight activation by pressing any button does
not cause any other action than turning on the backlight.
8.1.5

How to set frequency and voltage and current gain factors

Frequency, current and voltage gain for the stator and/or rotor can be set and stored from the injection
unit HMI. The display shows the latest stored settings.
The settings are stored in non-volatile memory, which means that they remain stored in case IED is
powered off.
78
1
1
2
2
System
System
f
f
STATOR
STATOR
f
f
UmaxEF
UmaxEF
ROTOR
ROTOR
f
f
Gain
Gain
Display content in normal operation
Status symbols and their description
Description of the status
Over voltage occurred, injection is blocked. This can occur on both X61/62
and X81/82 (Stator & Rotor) simultaneously or on either of them. The symbol
is displayed in the status column (column 1) in row 2 for X61/62 and in row 4
for X81/82. The injection is blocked until a manual reset of the blocking occurs.
Injection blocked by the injection switch. The symbol is displayed in the status
column (column 1) and is always shown in both row 2 and 4.
Injection blocked by binary input. Blocked injection will be shown in the status
column (column 1) depending on binary in status. This can occur on both
X61/62 then shown in row 2 and X81/82 then shown in row 4 (Stator & Rotor)
Ø
simultaneously or on ether of them.
Analog output saturation. This status is set when the analog signal, current
and or voltage, to REG670 IED is too high and may thereby be incorrect due
to saturation in amplifier stage. Saturation status will be shown in the status
column (column 1) in row 3 or 5 depending on the saturation occurrence
© 2017 - 2023 Hitachi Energy. All rights reserved
3
3
4
4
[Hz] :
[Hz] :
50
50
[Hz] :
[Hz] :
087
087
[V] :
[V] :
160
160
[Hz] :
[Hz] :
113
113
3
3
1MRK500127-UUS Rev. M
Priority
1
2
Over voltage
blocked status
overrides
displaying of this
status
3
Injection switch
and over voltage
blocked overrides
displaying of this
status
Not applicable
GUID-6F744ADD-B250-44E2-AFC6-6BFCFA43E8F9 v2
670 series
Operation manual