Section 4
Overview
The serial communication follows the EIA-485 standard and is intended to be used in multi-point
communication.
Disturbance files are accessed using the IEC 61850, IEC 60870-5-103, DNP, SPA, LON or FTP
protocols. The disturbances are in COMTRADE format. The IED can send binary signals to other IEDs
(so called horizontal communication) using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile or through LON network variables. Binary GOOSE messaging can, for example,
be employed for protection and interlocking-based protection schemes.
The IED meets the GOOSE performance requirements for tripping applications in transmission
substations, as defined by the IEC 61850 standard. Further, the IED supports the sending and receiving
of analog values using GOOSE messaging. Analog GOOSE messaging enables fast transfer of analog
measurement values over the station bus.
The IED interoperates with other IEC 61850 compliant IEDs, tools and systems and simultaneously
reports events to eight different clients on the IEC 61850 station bus. For a system using DNP3 over
TCP/IP, events can be sent to four different masters. For systems using IEC 60870-5-103 IED can be
connected to one master in a station bus with star-topology.
The IED has a number of communication ports which support different protocols:
Communication media
Ethernet (fiber-optic multimode LC connector 100BASE-FX
or 100BASE-TX with connector RJ45)
Optical Serial port (glass with ST connector or plastic with
HFBR snap-in connector)
Optical LON port (glass with ST connector or plastic with
HFBR snap-in connector)
RS485
The IED supports GPS, IRIG-B, PPS, SNTPv4 (RFC2030), PTP or Binary time synchronization methods
with a time-stamping resolution of 1 ms or better. Alternative time synchronization methods are LON,
SPA, DNP or IED 60870-5-103.
4.4

PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all
stages of the IED life cycle.
Planning
Engineering
Commissioning
Operation and disturbance handling
Functional analysis
32
When using PCM600 for writing to the IED, ensure that the LHMI is not in a menu position
where settings can be made. Only one active transaction, from LHMI or PCM600, is allowed
at a time.
© 2017 - 2023 Hitachi Energy. All rights reserved
Protocols supported
IEC 61850, FTP, C37.118, IEEE1344, PTP, HSR, PRP,
SNTPv4 (RFC2030)
IEC 60870-5-103, DNP3, SPA
LON
IEC 60870-5-103, DNP3
1MRK500127-UUS Rev. M
AMU0600443 v13
670 series
Operation manual