WIRING and ACCESSORIES

Power Supply

Fuse
PD
R
S
T
(+1)
( L1 )
( L2 )
( L3 )
P
(+)
Inverter
R0
RB
T0
N
(-)
( T1 )
( T2 )
( T3 )
U
V
W
Motor
IM
Motor Output
Input
Voltage
(kW(HP))
SJ700
0.4(1/2)
004LFUF2,LFF2
0.75(1)
007LFUF2,LFF2
1.5(2)
015LFUF2,LFF2
2.2(3)
022LFUF2,LFF2
3.7(5)
037LFUF2,LFF2
5.5(7.5)
055LFUF2,LFF2
7.5(10)
075LFUF2,LFF2
11(15)
110LFUF2,LFF2
200V
15(20)
150LFUF2,LFF2
18.5(25)
185LFUF2,LFF2
220LFUF2,LFF2
22(30)
30(40)
300LFUF2,LFF2
37(50)
370LFUF2,LFF2
45(60)
450LFUF2,LFF2
55(75)
550LFUF2,LFF2
75(100)
-
0.75(1)
007HFEF2,HFUF2,HFF2
015HFEF2,HFUF2,HFF2
1.5(2)
2.2(3)
022HFEF2,HFUF2,HFF2
3.7(5)
037HFEF2,HFUF2,HFF2
5.5(7.5)
055HFEF2,HFUF2,HFF2
7.5(10)
075HFEF2,HFUF2,HFF2
11(15)
110HFEF2,HFUF2,HFF2
15(20)
150HFEF2,HFUF2,HFF2
18.5(25)
185HFEF2,HFUF2,HFF2
22(30)
220HFEF2,HFUF2,HFF2
30(40)
300HFEF2,HFUF2,HFF2
37(50)
370HFEF2,HFUF2,HFF2
400V
45(60)
450HFEF2,HFUF2,HFF2
55(75)
550HFEF2,HFUF2,HFF2
750HFEF2,HFUF2,HFF2
75(100)
90(125)
900HFEF2,HFUF2,HFF2
110(150)
1100HFEF2,HFUF2,HFF2
132(175)
1320HFEF2,HFF2
150(200)
1500HFUF2
160(220)
-
185(250)
1850HFE2,HFU2,HF2
2200HFE2,HFU2,HF2
220(300)
315(400)
3150HFE2,HFU2,HF2
400(550)
4000HFE2,HFU2,HF2
Note 1: Field wiring connection must be made by a UL and c-UL listed closed-loop terminal connector sized for the wire gauge involved.
Connector must be fixed using the crimping tool specified by the connector manufacture.
Note 2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft).
Name
Input side AC reactor
EMI filter
Radio noise filter
Radio noise filter
(Capacitor filter)
DC link choke
Braking resistor
Braking unit
Output side noise filter
Radio noise filter
AC reactor
LCR filter
Note: An EMI filter is required for European EMC directive and RCM, but the others are not for this purpose.
Model
Power Lines
AWG
mm
2
L700
SJ700
-
14
2.1
-
14
2.1
-
14
2.1
-
14
2.1
-
10
5.3
-
8
8.4
-
6
13.3
110LFF
6
13.3
150LFF
33.6
2
185LFF
1
42.4
220LFF
1
42.4
300LFF
2/0
67.4
370LFF
4/0
107.2
450LFF
4/0
107.2
550LFF
2/0X2
67.4X2
750LFF
-
-
14
2.1
-
14
2.1
-
14
2.1
-
14
2.1
-
12
3.3
-
10
5.3
110HFF
8
8.4
150HFF
6
13.3
185HFF
6
13.3
220HFF
6
13.3
300HFF
3
26.7
370HFF
42.4
1
450HFF
1
42.4
550HFF
2/0
67.4
750HFF
1/0X2
53.5X2
900HFF
1/0X2
53.5X2
1100HFF
3/0X2
85.0X2
1320HFF
3/0X2
85.0X2
-
3/0X2
85.0X2
1600HFF
-
-
300X2
152X2
-
350X2
177X2
-
500X2
253X2
-
800X2
405X2
Function
This is useful in suppressing harmonics induced on the power supply
lines, or when the main power voltage imbalance exceeds 3% (and
power source capacity is more than 500kVA), or to smooth out line
fluctuations. It also improves the power factor.
Reduces the conducted noise on the power supply wiring generated by
the inverter. Connect to the inverter input side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise
(can also be used on output).
This capacitor filter reduces radiated noise from the main power wires in
the inverter input side.
Suppresses harmonics generated by the inverter.
This is useful for increasing the inverter's control torque for high
duty-cycle (on-off) applications, and improving the decelerating capability.
Reduces radiated noise from wiring in the inverter output side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise
(can also be used on input).
This reactor reduces the vibration in the motor caused by the inver-ter's
switching waveforms, by smoothing the waveforms to approxi-mate
commercial power quality. It is also useful when wiring from the inverter
to the motor is more than 10m in length, to reduce harmonics.
Sine wave shaping filter for the output side.
Wiring
Fuse
(Class J)
Signal
AWG
mm
2
Lines
L700
SJ700
L700
-
5
-
-
10
-
-
15
-
-
20
-
-
30
-
-
30
-
-
40
-
0.75mm
2
6
13.3
60
40
shielded
6
13.3
80
60
wire
2
33.6
100
80
1
42.4
125
100
1
42.4
150
125
2/0
67.4
175
150
4/0
107.2
225
175
4/0
107.2
250
225
2/0X2
67.4X2
-
250
-
5
-
-
10
-
-
10
-
-
15
-
-
15
-
-
15
-
8
8.4
20
30
6
13.3
30
40
6
13.3
40
50
6
13.3
50
60
3
26.7
50
70
0.75mm
2
1
42.4
60
90
shielded
1
42.4
70
125
wire
2/0
67.4
90
125
1/0X2
53.5X2
225
225
1/0X2
53.5X2
225
225
3/0X2
85.0X2
300
300
3/0X2
85.0X2
300
300
-
300
-
3/0X2
85.0X2
-
300
-
700
-
-
700
-
-
700
-
-
1000
-
26

Advertisement