[5] Inspection of numeric display
After closing the power source, the 4-digit display unit displays the following contents.
Power ON
Current output value
(Voltage mode)
6.2 Maintenance inspection
The eqipment does not contain any consumable parts which may run down in a short time.
•
The standard guidline replacement period of smoothin capacitor is 5 to 10 years.
Since the standard replacement period may vary, depending upon the magnitude of output current,
ambinient temperature or operation rate, place an order or smoothing capacitor from the Service Cen-
ter of Mitsubishi Electric as required.
The EEPROM ( used for storage of setting data ) is serviceable for 100,000 re-writing, and the power
•
source ON/OFF operation is limited to 100,000 times or less.
For periodical inspection, check for the following items;
•
Check that the panel temperatute is not unusually increased due to heating element, direct sun-
•
shine, etc.
Check that the powder dust or cuductive dust does not enter the panel.
•
Check that the wiring terminal is not loosened, and that there is not any other failure.
•
2sec
Voltage control mode
(DIP SW.4~10=ON)
2sec
Current control mode
(Example for DIP SW.4~10=3.2A)
Setting of other than above
Close the power source
after re-setting
2sec DIP SW.2=ON、
SW.3=ON
0~5V mode
DIP SW.2=ON、
2sec
SW.3=OFF
0~8V mode
DIP SW.2=OFF、
2sec
SW.3=ON
Free mode
Aux.power output
for 2 seconds.
Current output value
(Current mode)
18
< Display of output full-scale >
When the DIP SW4 to SW10 are all turned on,
•
the contents shown left is displayed for 2 sec-
onds. (It is invalid to change the switch ON/
OFF after turn on the power source.)
When the DIP SW4 to SW10 are set to 0.2 to
•
4.0A, the contents shown left is displayed for 2
seconds. (It is invalid to change the switch ON/
OFF after the closing the power source.)
The error is displayed exept when the DIP SW4
•
to SW10 are set to the other than above.
In such a case, turn on the power source after
setting the DIP SW4 to SW10 correctly.
< Display of input signal level >
When the DIP SW2 is turon on, the the input
•
signal level is set to 0 to 5V (SW3=ON), or set
to 0 to 8V ( SW3=OFF ), by which the current
setting value is displayed for 2 seconds as
shown left.
When the DIP SW2 is turned off and SW3 is
•
turned on, the input signal level is set by key
operation.
In this case, the current setting value is displayed
for 2 seconds as shown left.
When the DIP SW2 and SW3 are turned off, the
mode is set to the built-in variable resistor.
The current value of output voltage or output
•
current is displayed all the time as shown left.
2sec.
2sec.