Mitsubishi Electric 800 Series Instruction Manual page 20

Vector control terminal block
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Output signal
Terminal
Type
Common
symbol
Relay
A, B, C
Open
DO1 to
SE
collector
DO3
Analog
AM
5
FPA5
Encoder
pulse
FPB5
SD
dividing
output
FPZ5
Terminal name
1 changeover contact output that indicates that an
inverter's protective function has been activated
and the outputs are stopped.
Relay output
Fault: discontinuity across B and C (continuity
(fault output)
across A and C), Normal: continuity across Band C
(discontinuity across A and C)
The function of terminals can be changed with the
output terminal function selection (Pr.195).
The function can be assigned to an output terminal
Digital output terminal
by the output terminal function selection (Pr.190 to
1 to 3
Pr.192).
Outputs a selected monitored item (such as output
frequency) among several monitored items
according to the Pr.158 setting. The signal is not
output during an inverter reset.
Analog voltage output
The output signal is proportional to the magnitude
of the corresponding monitoring item.
Use Pr.55, Pr.56, and Pr.866 to set full scales for
the monitored output frequency, output current, and
torque.
Control terminal
Outputs A-, B- and Z-phase (home position and
option / Encoder A-
mark pulse) signals from the encoder. The A- and
phase output terminal
B-phase signals can be divided by the ratio (1/n)
Control terminal
and output.
option / Encoder B-
n=1 to 32767 (an integer)
phase output terminal
Use Pr.863 Encoder pulse division ratio for
Control terminal
division.
option / Encoder Z-
Common terminal is terminal SD.
phase output terminal
Terminal function description
PRE-OPERATION INSTRUCTIONS
Rated specification
Contact capacity: 230
VAC
0.3 A (power factor =
0.4)
1
30 VDC 0.3 A
Open collector output
Permissible load: 24 to
27 VDC, 0.1 A
Output signal: 0 to ±10
VDC
Permissible load
current: 1 mA
(load impedance: 10
kΩ or more)
Resolution: 13 bits
Open collector output
Permissible load: 24 to
27 VDC,
maximum 50 mA
19