3.3
Wiring of control circuit
3.3.1
Wiring method
1.
Refer to
page 35
and treat the wires.
2.
Loosen the terminal screw and insert the cable into the terminal.
3.
Tighten the screw according to the specified tightening torque.
Undertightening may cause cable disconnection or malfunction. Overtightening may cause a short circuit or malfunction
due to damage to the screw or unit.
Terminal name
A, B, C
0.5 N•m to 0.6 N•m
Other than the above
0.22 N•m to 0.25 N•m
Tightening torque
Small flathead screwdriver (Tip thickness: 0.4 mm/tip width: 2.5 mm )
Screwdriver
3
33
WIRING