Fujitsu ETERNUS AB Series Site Planning Manual page 16

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

1.
ETERNUS AB/HB Installation
Installation Specifications
Maximum
power
consumption
(*2)
Maximum
heat
generation
(*2)
Maximum
amount of
exhaust air
Item
Controller
3.5" type
shelf
2.5" type
Drive shelf
DE212C
3.5" type
DE224C
2.5" type
DE460C
60-drive
type
Maximum configuration
(*4)
Controller
3.5" type
shelf
2.5" type
Drive shelf
DE212C
3.5" type
DE224C
2.5" type
DE460C
60-drive
type
Maximum configuration
(*4)
Controller shelf
Drive shelf
2.5" type / 3.5" type
60-drive type
ETERNUS HB2100
AC100 – 120V
565 W (568 VA)
AC200 – 240V
565 W (568 VA)
AC100 – 120V
-
AC200 – 240V
-
AC100 – 120V
344 W (344 VA)
AC200 – 240V
344 W (344 VA)
AC100 – 120V
452 W (450 VA)
AC200 – 240V
452 W (450 VA)
AC100 – 120V
-
AC200 – 240V
1,460 W (1,466 VA)
AC100 – 120V
1,921 W (1,918 VA)
AC200 – 240V
4,945 W (4,966 VA)
AC100 – 120V
2,035 kJ/h
AC200 – 240V
2,035 kJ/h
AC100 – 120V
-
AC200 – 240V
-
AC100 – 120V
1,237 kJ/h
AC200 – 240V
1,237 kJ/h
AC100 – 120V
1,627 kJ/h
AC200 – 240V
1,627 kJ/h
AC100 – 120V
-
AC200 – 240V
5,256 kJ/h
AC100 – 120V
6,916 kJ/h
AC200 – 240V
17,803 kJ/h
-
-
-
16
ETERNUS HB2200
-
-
674 W (674 VA)
674 W (674 VA)
344 W (344 VA)
344 W (344 VA)
452 W (450 VA)
452 W (450 VA)
-
1,460 W (1,466 VA)
2,029 W (2,024 VA)
4,046 W (4,056 VA)
-
-
2,425 kJ/h
2,425 kJ/h
1,237 kJ/h
1,237 kJ/h
1,627 kJ/h
1,627 kJ/h
-
5,256 kJ/h
7,305 kJ/h
14,564 kJ/h
-
-
-
Site Planning Guide

Advertisement

Table of Contents
loading

Table of Contents