Figure 18 Power Distribution Unit (Ac24A/200V, 2U, 16 Outlets); Table 28 Specifications For Power Distribution Units (Ac24A/200-240V, 2U, 16 Outlets) - Fujitsu ETERNUS AB Series Site Planning Manual

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

1.
ETERNUS AB/HB Installation
Outlet/Socket Specifications
Power Distribution Unit (AC24A/200V, 2U, 16 Outlets)
There are 16 outlets and two inlets.
Estimate the maximum current consumption to supply power to all the connected devices using
one of the modules of the power distribution unit.

Figure 18 Power Distribution Unit (AC24A/200V, 2U, 16 Outlets)

Two inlets
Sixteen outlets
: The current rating in four of the outlets must be 12A or lower

Table 28 Specifications for Power Distribution Units (AC24A/200-240V, 2U, 16 Outlets)

Outlet
Inlet
Voltage rating/
Socket type
Socket type
Power cord
current rating
Plug type
(Socket)
(Socket)
length
IEC60320 C13
NEMA L6-30P
NEMA L6-30R
4.0m
Rating: 200-240V 24A
42
Site Planning Guide