330 Technical data

Terminal and entry data for the power cables

IEC

Input (except IP66 (UL Type 4X) with disconnect), motor, resistor and DC cable
entries, maximum wire sizes (per phase) and terminal screw sizes and tightening
torques ( T ) are given below.
Frame
Cable
size
entries
1)
Per
Ø
cable
type
pcs
m m
3-phase U n = 230 V
R1
1
30
R2
1
30
R3
1
30
R4 v2
1
45
R5
1
45
R6
1
45
R7
1
54
R8
2
45
3-phase U n = 400 or 480 V
R1
1
30
R2
1
30
R3
1
30
R4
1
45
R4 v2
1
45
R5
1
45
R6
1
45
R7
1
54
R8
2
45
R9
2
54
1) Maximum cable diameter accepted. For the entry plate hole diameters, see chapter
drawings (page
363).
L1, L2, L3, T1/U, T2/V, T3/W terminals
Max wire size
Min wire size
(solid/stranded)
(solid/stran-
2)
ded)
mm 2
0.2/0.2
0.5/0.5
0.5/0.5
1.5/1.5
6
25
95
2×50
0.2/0.25
0.5/0.5
0.5/0.5
0.5/0.5
1.5/1.5
6
25
95
2×50
2×95
T
mm 2
N·m
6/4
1.0
16/16
1.5
35/35
3.5
70
5.5
70
15
150
30
240
40
2×150
40
6/4
1.0
16/16
1.5
35/25
3.5
50
4.0
70
5.5
70
15
150
30
240
40
2×150
40
2×240
70
Grounding terminals
T
Max wire size
mm 2
N·m
16/16
1.5
16/16
1.5
35/35
1.5
35/35
2.9
-
2.2
180
9.8
180
9.8
180
9.8
16/16
1.5
16/16
1.5
35/35
1.5
35/35
2.9
35/35
2.9
3)
2.2
35/35
3)
9.8
185
3)
9.8
185
3)
9.8
2×185
3)
9.8
2×185
Dimension