6
7b
PE
8. Slide the cables through the holes in the cable entry and attach the grommets
to the holes (the motor cable to the right and the input power cable to the
left).
9. Connect the motor cable:
•
Ground the shield 360 degrees under the grounding clamps.
•
Connect the twisted shield of the cable to the grounding terminal (9a).
•
Connect the phase conductors of the cable to terminals T1/U, T2/V and
T3/W. Tighten the screws to the torque given in the table (9b).
Note 1 for frames R8...R9: If you connect only one conductor to the connector,
ABB recommends that you put it under the upper pressure plate. If you use
parallel power cables, put the first conductor under the lower pressure plate
and the second under the upper one.
Note 2 for frames R8...R9: The connectors are detachable but ABB does not
recommend that you detach them. If you do, detach and reinstall the connectors
as described in
Input power cable
10. Connect the input power cable as in step 9. Use terminals L1, L2, L3.
7a 7b
Detaching and reinstalling the connectors (page
Electrical installation – Global (IEC) 155
7a
PE
156).