Install New Door OR Door Adaptor
Figure 79
2TSA451009P0000 Rev-B
Remove existing compartment door(s) and remove hinge block using #2 Phillips headed
screw driver.
To install new door follow the instructions below:
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.
Rack out the existing legacy AKR breaker from the LVS.
Keep the door open for accessing the door mounting pads placed on the right side
wall in the LVS compartment.
Loosen the screws holding the mounting pads to the compartment frame.
Note
that this will
provide
access
for
removing
the
old
door
from
the
LVS
compartment.
Unpack the new door assembly and mount it on the compartment and secure via
placing the hinges and tightening the screws.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the new door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill circuit breaker.
For
ordering
the
new
door
depending
on
door
size
refer
to
document
2TSA451008P0000
DOOR INTERIOR VIEW
DOOR EXTERIOR VIEW
3.
To install OEM Door Adaptor Follow the instructions below:
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.