Figure 80
Rack out & Remove the existing legacy AK/AKR breaker from the LVS.
Unpack the new door Adaptor kit assembly
Modify the door cut out as per the new door cutout template.
Check the through-door racking with the new door assembly.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill Breaker.
For
detail
instructions
refer
document
2TSE431967R1000,
2TSE431968R1000
&
2TSE431996R1000
OEM Adaptor (Show as Example)
ALIGN WHTN CENTER
ALLOW METH CENTER
fh LIME OF Ewa 2 RETROFIT BREAKER
LINE OF EWAX 2 RETROFIT BREAKER
/
TOR RH WINGED BOR
FoR LH HINGED book
\
/
we
Oo
I
\ \
4
ch
of
C
12
.
BREAMER
FASCIA
HAFCHED ARCA 10 BE
| CUT IN THE DOOR
\
'\
ORILE HOLES AS MARKED
STEP1
DOOR CUT OUT
SEE
NOTE
2
STEP 2
DOOR ASSEMBLY
SEE NOTE |
70| © 2020 Emax 2 Retrofill Circuit Breakers 800-5000A
2TSA451009P0000 Rev-B