ABB AKR30S-800A Installation And Maintenance Manual page 77

Retrofill circuit breakers
Table of Contents

Advertisement

A40-
Synchronizing 2K-1 signalling modul with the trip unit
e
The activation of local bus — essential to start the communication between the module
and the Trip unit
Figure 87
6
Classic View
DQ
saugata das@in abd.com
fil erm
GB
Unit configuration
O fatesh
TP App
a Status
HO
By verre
,
v
v
e
Once the local bus is activated 2k modue should synchronize with the Ekip touch trip
unit.
Check the following for synchronization status.
Power LED reports ON status and correct communication with Ekip Touch :
e
=©Off: module off
e
Fixed or flashing light synchronized on power LED of Ekip Touch: module ON and
communication with Trip unit present
e
Flashing not synchronized with power LED of Ekip Touch (two fast flashes per second):
module ON and communication with Trip unit absent
If the
Ekip
Signalling
2K
module
is detected
correctly
by
Ekip
Touch
the
specific
configuration area in the Modules Settings menu is activated.
For each Ekip Signalling 2K module detected by Ekip Touch, a specific menu is available
containing the submenus of all the available and configurable inputs and outputs.
Figure 88
2TSA451009P0000 Rev-B
©2020 Emax 2 Retrofill Circuit Breakers 800-5000A | 77