Mass Notification Mode of Operation

Latching
Type Code
(Y/N)
NOTE: For ACCL/ACCL+ detectors:
Detectors programmed as ACCL (P SUP) or ACCL+ (P SUP), the heat element will latch and require a system reset to clear. The Photo
element will latch or track, depending on the ACCL (P SUP) latching setting.
4
PHOTO/CO
*
Y
PHOTO/CO
Y
2,4,5
(P SUP)*,
,4
PHOTO/CO (C SUP)*
Y
NOTE: For Photo/CO detectors:
Detectors programmed as P/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will latch or track, depending on the
Photo/CO (Photo SUP) setting. Detectors programmed as P/CO (C SUP), the heat and Photo elements will latch and require a system reset to clear. The CO element will
latch or track depending on the Photo/CO (CO SUP) setting. For Photo/CO and CO Detectors programmed as Photo/CO (P SUP) or CO (CO SUP) will either latch
and track, depending on the setting.
* FlashScan only
CLIP Mode only
1
Requires approval of AHJ.
2
Not suitable for Canadian applications.
3
LED representation of a CO alarm may be performed using an ACS annunciator.
4
Photo element can be programmed as latching or tracking for all Photo/CO devices programmed as this type ID via VeriFire Tools.
5
3.4 Mass Notification Mode of Operation
3.4.1 How the Control Panel Indicates a Mass Notification Alarm
When an initiating device activates, the control panel does the following:
Produces a steady audible tone
Does not activate any alarm relays or devices programmed as Alarm Pending or General
Pending
Does not flash any panel LEDs
Displays a Type Code that indicates the type of device that activated the MN alarm
Displays
to the device, as shown below:
Status banner
Extended 12 character
custom label
NFS2-640 Operations P/N 52743:L4 06/10/19
Purpose
Indicates activation of the Photo, Heat, or CO element of a
detector.
Indicates activation of the Photo, Heat or CO element of a
detector.
Indicates activation of the Photo, Heat or CO element of a
detector.
Table 3.1 Fire Alarm Type Codes (3 of 3)
in the status banner on the LCD display, along with information specific
MN ALARM
Type Code of initiating device
M N A L M : E C S / M N M O N S E C U R I T Y S T A T I O N
M A I N B L G
Z 0 0 4
Zone
Lights
no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
Lights
light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools). FlashScan only. No Pre-Alarm
Lights
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools). FlashScan only. No Pre-
Alarm.
0 3 : 1 7 P 0 4 1 5 1 5 2 M 1 4 7
Time and date of trouble
Operation of the Control Panel
What it does
LED for photo and heat,
FIRE ALARM
LED for heat, no LED will
FIRE ALARM
LED for heat and photo
FIRE ALARM
Custom descriptor for
this device location
Device address
21