Viewing and Printing a Read Status
How to View Read Status for a Releasing Zone (R0-R9)
Releasing
Zone Number
next device
previous device
Zone status (ON or OFF)
How to Read Status for System Functions
NFS2-640 Operations P/N 52743:L4 06/10/19
Figure 4.5 Sample Special Zone Read Status Display
From the "Read Status" screen, press 0, then press the
key. You can now view the Read Status of a Releasing Zone as
follows: press Z, enter the zone number (R0-R9), then press the
ENTER
R0, enter Z, enter R0, then press the
panel now displays information for a Releasing Zone as shown
below.
Zone label for Releasing Function
O F F R E L E A S E F U N C T
D E L A Y = 0 0
A B O R T = U L I C R O S S = N S O K = 0 0 0 0 R 0 0
Selections for
Releasing Zone R0
Figure 4.6 Sample Releasing Zone Read Status Display
The "System Functions" screen specifies global settings for the con-
trol panel. From the "Read Status" screen, press 0, then press the
ENTER
follows: press Z, enter S0, press the
sample display and description of items for the Read Status of System
Functions:
S I L I N H = 0 0 0 A U T O = 0 0 0 V E R I F Y = 3 0 U S A T I M E
T E R M = N A C _ D L Y = Y L o c T B L I N K = 0 1 S T = 4 A C S = N
Parameter
SIL INH=000
Silence Inhibit timer in
seconds. Required in
Canada and some areas of
the USA.
AUTO=000
Auto Silence Timer in
seconds.
VERIFY=30
Alarm Verification Timer
USA TIME
Time and date display
format
TERM=N
Terminal supervision
AC_DLY=N
Delays AC loss reporting
Table 4.1 System Function Parameters (1 of 2)
key. For example, to read the status of Releasing Zone
R E L E A S E C O N T R O L
Indicates Special Zone R0
key. You can now view Read Status for System Functions as
Description
000 = no timer; or the timer duration in
seconds up to 300.
000 = no timer; 600-1200 seconds.
00 = no timer; 00-30 seconds.
USA TIME or EUR TIME
YES – To supervise the wiring of an
FDU-80.
NO – No FDU-80 supervision.
YES - AC loss reporting is delayed for
approximately 3 hours.
NO - No AC loss delay.
Read Status Operation
ENTER
key. The control
ENTER
key. Shown below is a
ENTER
Settings
47