Point and System Troubles Lists
TROUBLE MESSAGE
TYPE
PANEL DOOR OPEN
The panel door is open.
POWER SUPPLY COMM
There has been a communication failure with the power
FAIL
supply.
PROGRAM CORRUPTED
The database that houses the panel's programming is
corrupt.
PROGRAM MODE
A user is currently accessing the panel's programming
ACTIVATED
menus.
RELEASE DEV. DISABLE
Releasing devices have been disabled.
SELF TEST FAILED
Diagnostic test failed.
CLASS A POS. LOOP x
There is an open circuit on the positive side of loop x. Class A and Class X are supervised methods of
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as
a Class A trouble until you correct the condition and press
use of ISO-X isolator modules.
CLASS A NEG. LOOP x
There is an open circuit on the negative side of loop x. Class A and Class X are supervised methods of
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as
a Class A trouble until you correct the condition and press
use of ISO-X isolator modules.
CLASS A SHORT LOOP x
Class A and Class X are supervised methods of communicating with addressable devices. If the control panel
detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in an
unsupervised method. The latching trouble will display on the panel as a Class A trouble until you correct the
condition and press
SYS INITIALIZATION
The devices are initializing.
TERM. SUPERVISORY
There is a communication error with the CRT-2.
UDACT NO ANSWER
The UDACT or UDACT-2 is not responding.
UDACT TROUBLE
The UDACT or UDACT-2 is in trouble.
* This trouble may be fire panel or backup battery related. Test and replace backup batteries if necessary/
78
SYSTEM TROUBLES
TROUBLE DESCRIPTION
. Class X configuration of the SLC requires the use of ISO-X isolator modules.
RESET
Table D.2 System Troubles
ACTION
Close door.
Service is required.
The database must be re-downloaded, or all
programming must be cleared and re-entered. If the
trouble still does not clear, contact Technical Services.
No action is required / Exit the Programming mode.
Enable the devices.
Call Technical Services.
. Class X configuration of the SLC requires the
RESET
. Class X configuration of the SLC requires the
RESET
No action is required, as the trouble will clear when
initialization is completed. However, devices will not
report off-normal events while this trouble exists.
Check connections to the CRT-2 terminal.
Determine whether the UDACT/UDACT-2 is
functional, and connected and addressed properly.
Determine if the UDACT/UDACT-2 is functional and
wired correctly.
NFS2-640 Operations P/N 52743:L4 06/10/19
System Troubles