Honeywell NOTIFIER NFS2-640 Operation Manual page 21

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-640:
Table of Contents

Advertisement

Operation of the Control Panel
Latching
Type Code
(Y/N)
WATERFLOW S
Y
RF SUPERVSRY
N
LATCH SUPERV
Y
TRACK SUPERV
N
SPRINKLR SYS
Y
TAMPER
Y
SUP.T(DUCTI)
N
SUP.L(DUCTI)
Y
SUPT(DUCTL)
N
SUPL(DUCTL)
Y
SUP.T(DUCTP)
N
SUP.L(DUCTP)
Y
SUPT(PHOTO)
N
SUP.L(PHOTO)
Y
SUP.T(ION)
N
SUP.L(ION)
Y
SUP.L(LASER)
Y
N
SUP.T(LASER)
P/CO (C SUP)*
Y
P/CO (P SUP)*
Y
NOTE: For Photo/CO detectors:
Detectors programmed as P/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will
latch or track, depending on the Photo/CO (Photo SUP) setting. Detectors programmed as P/CO (C SUP), the heat and Photo elements will
latch and require a system reset to clear. The CO element will latch or track depending on the Photo/CO (CO SUP) setting. For Photo/CO
and CO Detectors programmed as Photo/CO (P SUP) or CO (CO SUP) will either latch and track, depending on the setting.
ACCL (P SUP)
Y (see
note
below)
ACCL+ (P SUP)
Y (see
note
below)
NOTE: For ACCL/ACCL+ detectors:
Detectors programmed as ACCL (P SUP) or ACCL+ (P SUP), the heat element will latch and require a system reset to clear. The Photo
element will latch or track, depending on the ACCL (P SUP) latching setting.
*FlashScan only
30
Monitor Modules
Purpose
Indicates supervisory condition for activated waterflow switch Lights
Monitors a radio frequency device
Indicates latching supervisory condition
Indicates tracking supervisory condition
Indicates activation of sprinkler system
Indicates activation of tamper switch
Detectors
Ion detector that indicates supervisory (non-alarm) condition
Ion detector that indicates supervisory (non-alarm) condition
Laser detector that indicates supervisory (non-alarm) condition Lights
Laser detector that indicates supervisory (non-alarm) condition Lights
Photo detector that indicates supervisory (non-alarm) condition Lights
Photo detector that indicates supervisory (non-alarm) condition Lights
Photo detector that indicates supervisory (non-alarm) condition Lights
Photo detector that indicates supervisory (non-alarm) condition Lights
Ion detector that indicates supervisory (non-alarm) condition
Ion detector that indicates supervisory (non-alarm) condition
Laser detector that indicates supervisory (non-alarm) condition Lights
Laser detector that indicates supervisory (non-alarm) condition Lights
Indicates activation of the Photo, Heat or CO element of a
detector. LED representation of a CO alarm may be performed
using an ACS annunciator.
Indicates activation of the Photo, Heat or CO element of a
detector. FlashScan only. No Pre-Alarm. Requires approval of
AHJ. LED representation of a CO alarm may be performed
using an ACS annunciator. Photo element can be programmed
as latching or tracking for all Photo/CO devices programmed
as this type ID via VeriFire Tools.
Combination Photoelectric/Heat detector. Photo element
activation generates a supervisory condition FlashScan only.
No Pre-Alarm.
Combination Photoelectric/Heat detector with low temperature
warning. Photo element activation generates a supervisory
condition. FlashScan only. No Pre-Alarm.
Table 3.4 Supervisory Type Codes
Active Supervisory Signal Mode of Operation
What it does
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
LED and activates CBE
SUPERVISORY
Activation of the Heat or Photo elements will
light an indicator at the control panel.
Activation of the CO element will light the
LED. Activates CBE.
SUPERVISORY
Activation of the Heat element will light an
indicator at the control panel.
Activation of the CO element will not light
and indicator at the control panel.
Activation of the Photo element will light the
LED. Activates CBE.
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
Lights
LED and activates CBE
SUPERVISORY
NFS2-640 Operations P/N 52743:L4 06/10/19

Advertisement

Table of Contents
loading

Table of Contents