Chapter 2
If you use a wall socket directly without a UPS or PDU, be sure to check power
requirements against the amperage rating of your electrical system. See the
section titled "Site Preparation: Circuit Breakers. " If your electrical system has
the capacity to power the components, plug the HP NetServer LH 4r and mass
data storage units into NEMA 5-15 receptacles using the 90-inch (approximately
230 cm) power cords supplied.
Table 2-3. 120 VAC PDU Power and Current
Component
(Note 1, 2, 3)
120 VAC PDU
HP NetServer
LH 4r
HP NetServer
Rack Storage/12
HP NetServer
Rack Storage/8
HP Console
Switch
15-21 inch
Monitor
Note 1 Power figures shown in this table are for 120 VAC. For 100 VAC data,
see Table 3-4.
Note 2 More ratings for 120 VAC are listed in Table 3-5. For a full list of power ratings,
see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 3 Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
30
Connecting and Routing Cables to the HP NetServer LH 4r
Model
E7675A
D7093A (400 MHz/512)
D7095A (400/1M)
D6970A (450 MHz/512)
D6972A (450 MHz/1M)
D5989A
D4902A
J1497A
varies
Input
Input
Current
Power
Power
(A)
(VA)
(W)
N/A
N/A
maximum
16
1160
1130
9.7
548
537
4.5
211
209
2.0
42
29
0.3
200
140
1.2