HP D7171A - NetServer - LPr Manual page 37

Rack cabling reference
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 2
Table 2-5. 200/208 VAC PDU Power and Current
Component
(Note 1, 2)
200/208 VAC
PDU
HP NetServer
LH 4r
HP NetServer
Rack Storage/12
HP NetServer
Rack Storage/8
HP Console
Switch
15-21 inch
Monitor
Note 1 More ratings are listed in Tables 3-6 (200/208 VAC). For a full list of power
ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web
Site.
Note 2 Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 200/208 VAC Configuration
Figure 2-9 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the
rack: two (on the right rear) NEMA 5-15 providing 120 VAC, two L6-20R, and
one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a
detachable cord with an L6-20P plug. This cord connects to the PDU with an
IEC 320 C19 plug. The 208 VAC PDU has two IEC 320, C19 and six IEC 320,
C13 receptacles. A second PDU (E7672A) is available, which can be daisy-
chained to the 16-amp unit, providing ten more C13 receptacles. The fan (not
required if perforated doors--or no doors--are used front and back) plugs into one
of the C13 receptacles on the PDU.
Connecting and Routing Cables to the HP NetServer LH 4r
Model
E7671A or E7672A
D7093A (400 MHz/512)
D7095A (400/1M)
D6970A (450 MHz/512)
D6972A (450 MHz/1M)
D5989A
D4902A
J1497A
varies
Input
Input
Current
Power
Power
(A)
(VA)
(W)
N/A
N/A
maximum
16
1130
1100
5.7
548
537
2.6
211
209
1.1
42
29
0.2
200
140
0.7
33