Am And Ami Terminals (C028, C029, C106, C108 To C110) - Hitachi L700 SERIES Instruction Manual

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

4.2.82 AM and AMI terminals
You can monitor the inverter output frequency and output current via the AM
and AMI terminals on the control circuit block.
The AM terminal outputs an analog voltage signal (0 to 10 V).
The AMI terminal outputs an analog current signal (4 to 20 mA).
(1) AM siginal selection /AMI signal selection
Select the signals to be output from the AM and AMI terminals among those shown below.
Item
Function code
[AM] siginal
selection /
C028/C029
[AMI] siginal
selection
*1 This signal is output only when the V/F characteristic curve selection (see Section 4.2.17) is the
sensorless vector control.
*2 The specifications of the output torque (signed) are as follows:
AM output (V)
10
5
0
*3 For detail of the function, refer "Programing software Ez-SQ user manual".
(2) AM/AMI adjustment
Adjust the inverter output gain for the external meters connected to the AM and AMI terminals.
Item
Setting of the gain for AM monitoring
Setting of the offset for AM monitoring
Setting of the gain for AMI monitoring
Setting of the offset for AMI monitoring
Note: The offset data is in percentage (%).
(Example) When the current range of AMI terminal output is 4 to 20 mA (default), the offset of 4 mA
is 20%.
Data
00
Output frequency
01
Output current
02
Output torque (*1)
04
Output voltage
05
Input power
Electronic thermal
06
overload
07
LAD frequency
09
Motor temperature
10
Heat sink temperature
11
Output torque (signed)
13
General analog YA (1) (*4)
14
General analog YA (2) (*4)
When the AM gain (C106) is 100%
When the AM gain (C106) is 200%
When the AM offset (C109) is 50%
Torque (%)
100
200
Function code
C106
C109
C107
C110
Chapter 4 Explanation of Functions
Description
0 to maximum frequency (Hz) (*3)
0 to 200%
0 to 200%
0 to 133% (75% of full scale is
equivalent to 100%)
0 to 200%
0 to 100%
0 to maximum frequency (Hz)
0ºC to 200ºC (0ºC is output when the
motor temperature is 0ºC or less.)
0ºC to 200ºC (0ºC is output when the
motor temperature is 0ºC or less.)
(Output only from the AM terminal) 0
to 200% (*1) (*2)
(Output only from the AM terminal) 0
to 100%
(Output only from the AMI terminal) 0
to 100%
Range of data
50. to 200. (%)
Setting of the gain for AM monitoring
0 to 100 (%)
Setting of the offset for AM monitoring
50. to 200. (%)
Setting of the gain for AMI monitoring
0 to 100 (%)
Setting of the offset for AMI monitoring
4 - 77
Related code
C028: [AM] siginal selection
C029: [AMI] siginal selection
C106: AM gain adjustment
C109: AM offset adjustment
C108: AMI gain adjustment
C110: AMI offset adjustment
Full-scale value
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents