Communication Functions - Hitachi L700 SERIES Instruction Manual

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Chapter 4 Explanation of Functions

4.3 Communication Functions

The inverter can engage in RS485 communications with an
external control system that is connected to the TM2 terminal
block (on the control circuit terminal block board) of the inverter.
The L700 series inverter shares the ASCII communication
protocol with the SJ300 and L300P series inverters.
(1) Communication specifications
Item
Transmission speed
Communication method
Synchronization method
Transmission code
Transmission method
Applicable interface
Data bit length
Parity
Stop bit length
Initiation method
Waiting time
Connection format
Error check
<Specifications and connections of RS485 ports>
For the RS485 communication function, use the TM2 terminal block on the control circuit terminal block
board.
Followings are recommended as the wire to connect TM2.
Solid-core wire
0.14mm
Standard wire
0.14mm
Standard wire with bar terminal
Striped covering length 5mm
Screw torque 0.22Nm-0.25Nm(screw size M2)
ASCII mode
2,400, 4,800, 9,600, or 19,200 bps
Half-duplex communication
Start-stop transmission
ASCII code
Transmission beginning with the lowest-order bit
RS485
7 or 8 bits
No parity, even parity, or odd parity
1 or 2 bits
Initiation only by a command from the external
control system
10 to 1,000 ms
1-to-N connection (N: Maximum of 32 [inverters])
Overrun, framing, BCC,
vertical parity, and
longitudinal parity errors
Control circuit block
2
2
-1.5mm
(when two wires are on one terminal pole,0.14 mm
2
2
-1.0mm
(when two wires are on one terminal pole,0.14 mm
2
0.25mm
-0.5mm
A001: Frequency source setting
A002: Run command source setting
C071: Communication speed selection
C072: Node allocation
C073: Communication data length selection
C074: Communication parity selection
C075: Communication stop bit selection
C078: Communication wait time
C079: Communication mode selection
Modbus-RTU mode
Asynchronous
transmission
Binary code
8 bits
0 to 1,000 ms
Overrun, framing,
CRC-16, and
longitudinal parity errors
Abbreviated
name of
terminal
SN
RP
SN
Control circuit
block board
2
(example:PC-1.25 F-7 made by J.S.T.Mfg.Co.,Ltd)
4 - 98
Related code
Remarks
Selection with the digital operator
Selection with the digital operator
Selection with the digital operator
Selection with the digital operator
Setting with the digital operator
Station number to be selected
with the digital operator
Description
Positive signal terminal
SP
for transmission
Negative signal terminal
for transmission
Terminal to enable the
terminating resistor
Terminal to enable the
terminating resistor
2
-0.5mm
2
-0.2mm
2
)
2
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents