Function name
No.
1236h
(Reserved)
1237h
(Reserved)
1238h
Jog frequency setting
1239h
Jog stop mode
123Ah
(Reserved)
Torque boost method
123Bh
selection
123Ch
Manual torque boost value
Manual torque boost
123Dh
frequency adjustment
V/F characteristic curve
123Eh
selection, 1st motor
123Fh
V/f gain setting
Voltage compensation gain
1240h
setting for automatic torque
boost, 1st motor
Slippage compensation gain
1241h
setting for automatic torque
boost, 1st motor
1242h
(Reserved)
to1244h
1245h
DC braking enable
1246h
DC braking frequency setting
1247h
DC braking wait time
DC braking force during
1248h
deceleration
DC braking time for
1249h
deceleration
DC braking/edge or level
124Ah
detection for [DB] input
124Bh
DC braking force for starting
124Ch
DC braking time for starting
DC braking carrier frequency
124Dh
setting
124Eh
(Reserved)
124Fh
Frequency upper limit setting
1250h
Frequency lower limit setting
1251h
1252h
Jump (center) frequency
setting 1
1253h
1254h
Jump (hysteresis) frequency
1255h
width setting 1
Jump (center) frequency
1256h
setting 2
1257h
Jump (hysteresis) frequency
1258h
width setting 2
Jump (center) frequency
1259h
setting 3
125Ah
Jump (hysteresis) frequency
125Bh
width setting 3
Acceleration stop frequency
125Ch
setting
125Dh
Acceleration stop time
125Eh
frequency setting
Function code
R/W
-
-
Inaccessible
-
-
Inaccessible
A038
R/W "Start frequency" to 999
0 (free-running after jogging stops [disabled during
operation])
1 (deceleration and stop after jogging stops [disabled
during operation])
2 (DC braking after jogging stops [disabled during
operation])
A039
R/W
3 (free-running after jogging stops [enabled during
operation])
4 (deceleration and stop after jogging stops [enabled
during operation])
5 (DC braking after jogging stops [enabled during
operation])
-
-
A041
R/W 0 (manual torque boost), 1 (automatic torque boost)
A042
R/W 0 to 200
A043
R/W 0 to 500
0 (VC), 1 (VP), 2 (free V/f),
A044
R/W
3 (sensorless vector control)
A045
R/W 20 to 100
A046
R/W 0 to 255
A047
R/W 0 to 255
-
-
Inaccessible
A051
R/W 0 (disabling), 1 (enabling), 2 (set frequency only)
A052
R/W 0 to 40000
A053
R/W 0 to 50
A054
R/W 0 to 70
A055
R/W 0 to 600
A056
R/W 0 (edge operation), 1 (level operation)
A057
R/W 0 to 70
A058
R/W 0 to 600
A059
R/W 5 to 120
-
-
Inaccessible
0 or "maximum frequency limit" to "maximum
A061 (high)
R/W
frequency"
A061 (low)
R/W 0 or "maximum frequency limit" to "maximum
frequency"
A062 (high)
R/W
A062 (low)
R/W
0 to 40000
A063 (high)
R/W
A063 (low)
R/W
0 to 1000
A064
R/W
A065 (high)
R/W 0 to 40000
A065 (low)
R/W
0 to 1000
A066
R/W
A067 (high)
R/W 0 to 40000
A067 (low)
R/W
0 to 1000
A068
R/W
A069 (high)
R/W 0 to 40000
A069 (low)
R/W
0 to 600
A070
R/W
4 - 131
Chapter 4 Explanation of Functions
Monitoring and setting items Data resolution
Register
No.
-
-
0.01 [Hz]
-
-
-
0.1 [%]
0.1 [%]
-
1 [%]
1 [%]
1 [%]
-
-
0.01 [Hz]
0.1 [sec.]
1 [%]
0.1 [sec.]
-
1 [%]
0.1 [sec.]
0.1 [kHz]
-
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.1 [sec.]