DIP switch settings for Hydro Kit High temperature (K3)
Figure 57: Hydro Kit High Temperature DIP Switch Block
Table 13: Hydro Kit High Temperature DIP Switch Settings and Description

DIP Switch Setting - Hydro Kit High Temperature

Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Pre-coMMIssIoNING
Figure 57 along with Table 13 below outlines the correct positioning
of each DIP switch depending on the functioning of the Hydro Kit
unit. These settings are specific to the Hydro Kit High Temperature
(K3) unit.
Always turn off electric power before adjusting DIP switch settings. There
is a risk of electric shock if not turned off.
Guidelines
• DIP switch in the LEFT position is OFF. If it is in the RIGHT posi-
tion it is ON (as seen in Figure 57).
• Never place DIP switch #2 RIGHT/ON and DIP switch #3 LEFT/
OFF.
• Follow DIP switch settings in table precisely or unit may not oper-
ate properly.