Emergency Operation - LG ARNH963K2A2 Installation Manual

Hydro kit medium temperature (k2) btu/h 107,500; hydro kit high temperature (k3) btu/h 86,000
Hide thumbs Also See for ARNH963K2A2:
Table of Contents

Advertisement

The following function buttons can still be operated during emergency operation of each of the Hydro Kits.
Power ON/OFF
Button
Temperature View
Mode button (*)
Change Temperature
Button (**)
Water Heating
Enable / Disable
Button
The following function buttons cannot be used during emergency operation of each of the Hydro Kits.
Operation Mode Selection
Button
Programming
Button
Temperature Setting Mode
Button
Simultaneous Error Codes or faults
There may be cases where multiple errors or faults will be tripped at the same time, or closely follow each other. At this point, the unit will
default operation and limit functionality based on the most severe fault. For example, if there is a slight operational fault but a major fault also
trips, the unit will operate at the safest level that it can during the major fault incident. As an example, the hot water heating might not work in
an Emergency Operation mode due to a more severe fault that prevents it from warming. You might need to check the Domestic Hot Water
(DHW) sensor and related wiring to trace any troubleshooting issues.
If the Hydro Kit is operating in Emergency (Safe) Mode, automatic re-
start is disabled. If there is a loss of power during Emergency Mode; the
unit must be re-started manually. Under normal operating conditions, the
Hydro Kit is designed to automatically start up (reboot) once power is
restored.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
uNIt oPeratIoN
(*) Temperature measured by failed sensor is displayed as '--'
(**) Note that the unit cannot be turned off by setting the temperature
at the remote controller. It is only turned off by the thermostat signal.

Emergency Operation

71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arnh763k3b2

Table of Contents