LG ARNH963K2A2 Installation Manual page 65

Hydro kit medium temperature (k2) btu/h 107,500; hydro kit high temperature (k3) btu/h 86,000
Hide thumbs Also See for ARNH963K2A2:
Table of Contents

Advertisement

temperature control Parameter setting for sanitary Water Heating operation
Hydro Kit Medium temperature - continued
function Code 2C - Setting Water flow rate
Setting the value determines the temperature range of the input and output water flow rate. Value #1 of Function Code 2C: Water flow rate
which flows to the Hydro Kit. Refer to Table 16 for settings.
Table 16: Water Flow Rate Setting Value
Setting Value
Water flow rate
50
45~50
55
51~55
60
56~60
65
61~65
70
66~70
75
71~75
80
76~80
85
81~85
90
86~90
92
91~92
function Code 2E and 2f
Changing Thermal ON/OFF Temperature gap. Refer to Table 17 and Table 18 for the two types of thermal temperature values.
Table 17: Room Air Temperature
Thermal on
0
-0.9°F (-0.5°C)
1
7.2°F (4°C)
2
3.6°F (2°C)
3
-1.8°F (-1°C)
function Code 30
Displays Remote Controller Program Version when selected.
(l/min)
Thermal off
2.7°F (1.5°C)
10.8°F (6°C)
7.2°F (4°C)
1.8°F (1°C)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Pre-coMMIssIoNING
Function Codes - Hydro Kit Medium Temperature
Table 18: Leaving Water Temperature and DHW Temperature
Thermal on
0
-3.6°F (-2°C)
1
-10.8°F (-6°C)
2
-3.6°F (-2°C)
3
-1.8°F (-1°C)
Thermal off
3.6°F (2°C)
7.2°F (4°C)
7.2°F (4°C)
1.8°F (1°C)
65