Rack-Mounting Requirements - HP A10500 Series Installation Manual

Hide thumbs Also See for A10500 Series:
Table of Contents

Advertisement

Table 2 Humidity requirements
Humidity
Operating humidity
Storage humidity
Table 3 Dust concentration limit in the equipment room
Substance
Dust particles
NOTE:
Dust particle diameter ≥ 5 μm
Table 4
Limits on harmful gases in the equipment room
Gas
Maximum concentration (mg/m
SO
0.2
2
H
S
0.06
2
NH
0.05
3
Cl
0.01
2

Rack-mounting requirements

Before rack-mounting a switch, make sure the rack meets the following requirements:
HP recommends that you mount a switch in an open rack. If you mount a switch in a closed rack,
make sure there is a good heat dissipation system.
The rack is steady enough to support the switch and accessories.
The switch fits the rack size. Leave some space beside the left and right panels of the switch for
chassis heat dissipation.
Range
10% to 95%, noncondensing
5% to 95%, noncondensing
Concentration limit (particles/m3)
≤ 3 x 10
4
(No visible dust on desk in three days)
3
)
2