Mitsubishi Electric F700 Instruction Manual page 104

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Parameter
Name
RS-485
331
communication
station number
RS-485
332
communication
speed
RS-485 communication
333
stop bit length
RS-485 communication
334
parity check selection
RS-485 communication
335
retry count
RS-485
336
communication
check time interval
RS-485 communication
337
waiting time setting
Communication
338
operation command
source
Communication
339
speed command
source
RS-485 communication
341
CR/LF selection
Communication
342
EEPROM write
selection
Communication
343
error count
Modbus-RTU
communication
539
check time interval
Protocol selection
549
NET mode
operation command
550
source selection
PU mode operation
command source
551
selection
Incre
Initial
Range
ments
Value
Set the inverter station number.
0 to 31
(same specifications as Pr.117 ) When "1"
1
0
(Modbus-RTU protocol) is set in Pr.551, the
(0 to 247)
setting range within parenthesis is applied.
3, 6, 12, 24,
Used to select the communication speed.
1
96
48, 96, 192,
(same specifications as Pr.118)
384
Select stop bit length and data length.
1
1
0, 1, 10, 11
(same specifications as Pr.119)
Select the parity check specifications.
1
2
0, 1, 2
(same specifications as Pr.120)
Set the permissible number of retries at
0 to 10,
1
1
occurrence of a data receive error. (same
9999
specifications as Pr.121)
RS-485 communication can be made, but
0
the inverter will come to trip in the NET
operation mode.
0.1s
0s
0.1 to
Set the communication check time interval.
(same specifications as Pr.122)
999.8s
9999
No communication check
Set the waiting time between data
0 to 150ms,
1
9999
transmission to the inverter and response.
9999
(same specifications as Pr.123)
Operation command source
0
communication
1
0
1
Operation command source external
0
Speed command source communication
Speed command source external (Frequency
1
setting from communication is invalid,
1
0
terminal 2 and 1 setting from external is valid)
Speed command source external (Frequency
2
setting from communication is valid, terminal
2 and 1 setting from external is invalid)
Select presence/absence of CR/LF. (same
1
1
0, 1, 2
specifications as Pr.124)
Parameter values written by communication
0
are written to the EEPROM and RAM.
1
0
Parameter values written by
1
communication are written to the RAM.
Displays the number of communication
errors during Modbus-RTU communication.
1
0
(read only)
Read only.
Displayed only when Modbus-RTU protocol
is selected.
Modbus-RTU communication can be made,
0
but the inverter will come to trip in the NET
operation mode.
0.1 to
0.1s
9999
Set the interval of communication check time.
(same specifications as Pr. 122)
999.8s
No communication check (signal loss
9999
detection) is made)
Mitsubishi inverter
0
(computer link)
protocol
1
0
Modbus-RTU
1
protocol
0
Communication option valid
1
Inverter RS-485 terminal valid
Automatic recognition of the
1
9999
communication option
9999
Normally, the RS-485 terminals are valid.
Communication option is valid when the
communication option is mounted.
Select the RS-485 terminals as the PU
1
operation mode control source.
1
2
Select the PU connector as the PU
2
operation mode control source.
Parameter list
Para
meter
copy
Description
×
After setting change,
reset (switch power off,
then on) the inverter.
The setting change is
reflected after a reset.
All
Para
para
meter
meter
clear
clear
: enabled
× : disabled
×
×
4
97